Requirements:
- Must be used with an equal or greater amount of soffit ventilation
- X18 installs on pitches 3/12 to 16/12.
- If ridge beam is wider than 2", call Customer Service at 800-346-7655.
|
|
|
Step
1: Cut
a slot in plywood along roof ridge 2" wide (1" on each side).
If ridge beam is present, cut slot 1" wide on each side of ridge beam.
Allow for a closed area of sheathing 12" at both ends of ridge. |
|

|
|
|
Step 2:
Place first
piece of vent with female end 1" in from gable end and use centering
line for proper alignment along peak. Fasten using at least two nails at
each end and in middle of section in nail line area (2 1/2" minimum
nail length). More may be required on steeper slopes to seat properly. Continue
installing additional pieces along ridge sliding female end over male end,
aligning using centering line. NOTE: In cold weather, allow a 1/8"
gap between vent sections for expansion. |
|

|
|
|
Step 3: When reaching the other
end, the last vent section may need to be cut to length. End plugs are provided
every 12" on underside of the product. Measure amount needed to install
to within 1" of gable end. Cut that length in from end of vent section
and flip around so that end plug is at gable end. Allow male tab from previous
piece to slide under last piece and nail in place. |
|

|
|
|
Step 4: Place first cap shingle over vent so that it overhangs
at least 1" over end of vent section. Install with 2 1/2" nails
in nail line area as you work your way down the roof. Cut last cap shingle
so that it overhangs vent 1" at other gable end. |
|
 |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|